Overall
Electric Meter Test Results
This
is a history of meters tested at the XXXXXXX Electric Test Shop.
Most of the meters were tested on a RFL 5800 others were tested on
a Weco 2300 automated test board. Both of these standards were
tested yearly.
These
meters consist of new meters as they were purchased and the meters
before they were disposed of at the end of their service life as
well as meters that were brought in from the field for testing. As
of 5/9/2012 the city test 100% of the meters. The time
span of these range from 1995 to 5/9/2012. Meters that were field
tested may be included at a later date, still need to tabulate
that data.
The
data for these results came from the databases of both standards.
All units are in percent registration. Total meters tested =
10,525.
|
|
Form
2S meters
|
|
Number
of meters = 8761
|
|
FL
|
99.77
%
|
|
PF
|
99.06
%
|
|
LL
|
98.55
%
|
|
|
Form
3S meters
|
|
Number
of meters = 83
|
|
FL
|
99.98
%
|
|
PF
|
99.91
%
|
|
LL
|
99.95
%
|
|
|
Form
5S meters
|
|
# of meters = 149
|
|
FL
|
99.72
%
|
|
PF
|
99.57
%
|
|
LL
|
99.08
%
|
|
|
Form
6S meters
|
|
Number
of meters = 12
|
|
FL
|
99.54
%
|
|
PF
|
99.95
%
|
|
LL
|
99.75
%
|
|
|
|
Form
8S meters
|
|
Number
of meters = 5
|
|
FL
|
99.66
%
|
|
PF
|
99.52
%
|
|
LL
|
99.83
%
|
|
|
Form
9S meters
|
|
# of meters = 590
|
|
FL
|
99.86
%
|
|
PF
|
99.99
%
|
|
LL
|
99.80
%
|
|
|
Form
10S meters
|
|
Number
of meters = 58
|
|
FL
|
93.81
%
|
|
PF
|
100.01
%
|
|
LL
|
100.18
%
|
|
|
Form
12S meters
|
|
# of meters = 287
|
|
FL
|
99.76
%
|
|
PF
|
99.49
%
|
|
LL
|
99.50
%
|
|
|
|
Form
14S meters
|
|
# of meters = 253
|
|
FL
|
100.03
%
|
|
PF
|
99.64
%
|
|
LL
|
99.27
%
|
|
|
Form
15S meters
|
|
Number
of meters = 6
|
|
FL
|
99.87
%
|
|
PF
|
99.70
%
|
|
LL
|
99.56
%
|
|
|
Form
16S meters
|
|
# of meters = 319
|
|
FL
|
99.84
%
|
|
PF
|
99.80
%
|
|
LL
|
99.77
%
|
|
|
Form
24S meters
|
|
Number
of meters = 2
|
|
FL
|
100.11
%
|
|
PF
|
100.15
%
|
|
LL
|
100.34
%
|
|
|